REACT Parasol Zenith
Chilled beam with integrated variable flow regulation
- Chilled beam with induced air opening in the bottom and 4-way horizontal discharge.
- Provides ventilation, cooling, and/or heating
- Designed to be installed in ceilings.
- Internal damper with 24-volt damper actuator for integration with room controls or BMS.
- The product is equipped with an actuator for flow adjustment, terminal block and air connection for flow measurement
- Simple commissioning because the flow measurement is performed directly in the air connection
- Pressure-independent flow regulation
- Can easily be integrated by a control equipment supplier via Modbus communication
- Large span between the lowest and highest air flow
- Few variants for easier sizing and variable air flow control
- Optimised for low energy consumption
- Manages high air flow at low driving pressure
- Easy installation on account of low weight, compact dimensions and optional air connections on short or long sides
- Hygiene design as an option for hospital applications
- Standard colour White RAL 9003
- Other colors upon request
| Variant | Supply air | Performance | |||
| Size ft. | Air connection in. | IN WG* | CFM | Total cooling capacity (BTUH)** | Sound level (dB(A)) |
| 2 | 5 | 0.3 | 42 | 1683 | 26 |
| 2 | 5 | 0.3 | 53 | 1925 | 28 |
| 2 | 5 | 0.3 | 64 | 2154 | 30 |
| 2 | 6 | 0.3 | 53 | 1932 | 27 |
| 2 | 6 | 0.3 | 74 | 2379 | 30 |
| 2 | 6 | 0.3 | 95 | 2761 | 33 |
| 4 | 5 | 0.3 | 53 | 3010 | 26 |
| 4 | 5 | 0.3 | 74 | 3676 | 28 |
| 4 | 5 | 0.3 | 95 | 4157 | 30 |
| 4 | 6 | 0.3 | 64 | 3072 | 23 |
| 4 | 6 | 0.3 | 127 | 4693 | 28 |
| 4 | 6 | 0.3 | 170 | 5430 | 34 |
| 6 | 8 | 0.3 | 127 | 5427 | 30 |
| 6 | 8 | 0.3 | 170 | 6451 | 33 |
| 6 | 8 | 0.3 | 212 | 7287 | 35 |
| * Total pressure duct (In wg) | |||||
| ** Air: ΔTl=12.6ºF / Water: ΔTmk=15.3ºF, twater=57.2/62.6ºF | |||||
Filter
Comprehensive detailed product information for the best selection and integration in project design
Installation, Operating, Maintenance and Safety information
Our products and services presented in an easy-to-access manner
Declarations and certificates etc
Wiring diagrams and hydraulic schemes etc
| Document | Article | Document type | Download |
|---|---|---|---|
| Description of functions & wiring diagrams – Gruner (pdf 3.87MB) | REACT ALS GMB, REACT M GMB, REACT P GMB, REACT PX GMB, REACT PX-SR GMB, REACT V GMB, REACT V-SR GMB | IOM Manual | |
| Environmental Product Declaration (pdf 606.98kB) | WISE, REACT and AWC control equipment for Chilled beams | Quality | |
| Declaration of conformity (CE) (pdf 102.79kB) | REACT Parasol Zenith e | Quality | |
| Comfort module with integrated variable flow regulation (pdf 6.05MB) | REACT Parasol Zenith e | Technical catalogue | |
| Chilled beam with integrated variable flow regulation (NA) (pdf 5.22MB) | REACT Parasol Zenith | Technical catalogue | |
| BACnet settings - Belimo (pdf 79.34kB) | REACT V BBAC | IOM Manual | |
| Installation - Commissioning - Maintenance (NA) (pdf 7.19MB) | REACT Parasol Zenith e | IOM Manual | |
| Installation, commissioning, maintenance (pdf 8.08MB) | REACT Parasol Zenith e | IOM Manual | |
| Eurovent certificate (pdf 197.65kB) | Chilled beams | Quality | |
| Modbus settings – Gruner (pdf 186.19kB) | REACT ALS GMB, REACT M GMB, REACT P GMB, REACT PX GMB, REACT PX-SR GMB, REACT V GMB, REACT V-SR GMB | IOM Manual |