You might want to visit our global site:
The CDR and CDD consist of two parts: a flat upper section with a connection spigot having a rubber sealing ring, and a removable diffuser face. Between the upper section and the diffuser face there is a slot which has two alternative positions. The diffuser face of the CDR is non-perforated that of the CDD is perforated. Both CDD and CDR are equipped with acoustic insulation.
The upper section is manufactured in galvanized sheet steel. The diffuser face is made of sheet steel. The complete diffuser is painted both internally and externally.
AIR FLOW - SOUND PRESSURE ROOM (Lp10A) *) | |||||||
CDR Size | 25 dB(A) | 30 dB(A) | 35 dB(A) | ||||
l/s | m3/h | l/s | m3/h | l/s | m3/h | ||
100 | 24 | 86 | 28 | 101 | 34 | 122 | |
125 | 32 | 115 | 37 | 133 | 44 | 158 | |
160 | 61 | 220 | 71 | 256 | 81 | 292 | |
200 | 80 | 288 | 91 | 328 | 105 | 378 | |
250 | 100 | 360 | 120 | 432 | 140 | 504 | |
315 | 140 | 504 | 165 | 594 | 190 | 684 | |
CDR Size | ALS Size | 25 dB(A) | 30 dB(A) | 35 dB(A) | |||
l/s | m3/h | l/s | m3/h | l/s | m3/h | ||
100 | 80-100 | 21 | 76 | 27 | 97 | 32 | 115 |
125 | 100-125 | 26 | 94 | 33 | 119 | 41 | 148 |
160 | 125-160 | 46 | 166 | 58 | 209 | 72 | 260 |
200 | 160-200 | 69 | 248 | 82 | 295 | 100 | 360 |
250 | 200-250 | 90 | 324 | 110 | 396 | 140 | 504 |
315 | 250-315 | 140 | 504 | 155 | 558 | 190 | 684 |
Data applies to 360° spread pattern. Data for CDR in combination with ALS commissioning box is stated for a total pressure drop of 50 Pa. *) Lp10A = Sound pressure incl. A-filter with 4 dB room attenuation and 10 m² room absorption area. |
Document | Article | Document type | Date | Download |
---|---|---|---|---|
Installation, commissioning, maintenance (pdf 777.11kB) | CDDb, CDRc | IOM Manual | 12/12/2022 | |
Circular ceiling diffuser for supply air - Flat upper section (pdf 1.25MB) | CDRc | Technical catalogue | 26/01/2023 | |
Air Overview Brochure (pdf 13.04MB) | Overview Brochure | Brochure | 26/09/2023 |